HT INDUSTRIAL AUTOMATION LIMITED

 
YOKOGAWA SS400G, SS300G MLSS Analyzers

YOKOGAWA SS400G, SS300G MLSS Analyzers

The SS400 MLSS analyzer is a measuring system best suited to continuously and consistently measure the concentration of mixed liquor suspended solids (MLSS) in an activated-sludge treatment process found in sewage or industrial wastewater treatment facilities.

The SS400G MLSS converter has a measuring range as wide as 500-20000 mg/l (ppm). Microprocessor-based, it has a wealth of self-diagnostic functions and alarm contact outputs like other converters in the EXA series, as well as excellent operability.

The SS300G MLSS sensor uses a measuring method that compares transmitted light with scattered light. The sensor is designed with due care to the arrangement of the optical system. These design features enable measurement of even low concentrations, making the sensor less susceptible to disturbing light. The optional jet or wiper cleaning unit permits continuous and consistent measurement even in an application where the sensor is exposed to contaminants.

A self-cleaning floating holder is available in addition to free-standing and immersion models, offering a wide range of choices according to the application needs.

 General Specification for SS400

 User's Manual for SS400G

 User's Manual for SS300G

Features

Converter

*

Wide output ranges, 0-1000 mg/l to 0-20000 mg/l.

*

Output in different two ranges.

*

Abundant contact outputs.

*

Enhanced self-diagnosis functions including failure in light source.

Sensor

*

Easy-to-maintain, lightweight, compact probe-like sensor.

*

Virtually no need for replacing light source and photodetector unit.

*

Pulse-driven light emission, eliminating effects of disturbing light.

*

Arrangement of optical system highly immune to effects of light reflecting from boundary surface.

*

Choice of wiper or jet cleaning unit.

*

Choice of various type of holders according to application needs.

Specifications

Converter

Measuring object

Concentration of mixed liquor suspended solids (MLSS) in an aeration tank in a sewage or industrial wastewater treatment plant

Measuring method

Transmitted/scattered light comparison method

Measuring range

500 to 20000 mg/l

Output signal

Two outputs, 4 to 20 mA DC; maximum load resistance: 600 Ω

Output range

Minimum 0 to 1000 mg/l
Maximum 0 to 20000 mg/l

Contact output

Four outputs

Contact input

Voltage-free contact for remote range selection and start of cleaning

Ambient temperature

-10 to 55

Relative humidity

10 to 90% RH (non-condensing)

Construction

Complies with JIS C0920 watertight, IEC IP65 and NEMA 4X standards

Supply voltage

100 to 240 V AC, 50/60 Hz, 24 V DC

Power consumption

22 VA maximum (AC power)
5 W maximum (DC power)

Weight

Approx. 2.5 kg

Sensor

Shape

Probe-like Sensor

Measuring object

Concentration of mixed liquid suspended solid (MLSS) in an aeration tank in a sewage or industrial wastewater treatment plant

Measuring principle

Scattered/transmitted light comparison method

Measuring range

500 to 20000 mg/l

Temperature of measured object

0 to 50

Pressure of measured object

0 to 200 kPa

Flow velocity

1 m/sec maximum

Cable length

3, 5, 10, 15 or 20 m

Material of wetted part or junction

Body; Stainless steel (304SS or equivalent)
Window; glass
O-ring; nitrile rubber
Cable; PVC

Weight

Approx. 0.5 kg plus N x 0.12 kg, where N is cable length

Cleaning unit (optional)

Wiper or jet cleaning
Note: No cleaning unit can be used if the sensor is equipped with a floating ball holder.

Material of wiper cleaning unit

Nitrile rubber and 304SS (wetted part)

Material of jet cleaning unit

Polypropylene, polyethylene and 304SS (wetted part)

Ambient temperature

-10 to 50

Construction

Complies with JIS rainproof standard

Performance

Linearity

±4.5 % F.S. (by stable kaolin)

Repeatability

2 % F.S. (by stable kaolin)

Stability

Zero: ±2 % F.S./day (by city water)
Span: ±2 % F.S./day (by calibration kit)

#
copyright 2009-2021  HT INDUSTRIAL AUTOMATION LIMITED