HT INDUSTRIAL AUTOMATION LIMITED

 
PROUDCTS:Home > Proudcts > DCS and Parts
ARS15B


YOKOGAWA
ARS15B 32 Solid State Inputs (SSR Built-In Type, M4 Terminals)


YOKOGAWA Relay Boards (for FIO):

ARM15A, ARM55D, ARM55W, ARM55T, ARM55C, ARS15B, ARS15M, ARS55M


GENERAL

This document describes the specifications of relay board used in FIO subsystem of CENTUM VP. Relay input/ output boards are connected in between digital input/output modules (for FIO) and field devices. Relay input boards receive contact signals or voltage input signals of field devices. Relay output boards receive output signals of the digital output module and amplify by the relay, and then output to field devices.   These relay boards support dual- redundant digital input/output modules (for FIO).


MODELS
 AND SUFFIX CODES


Solid
 State Relay Board

Description

Model

ARS15B

32 Solid State Inputs (SSR Built-In Type, M4 Terminals)

Sufx Codes

-5

For 48 V DC input

-6

110 V DC input

0

19-inch Rack Mountable

0

Basic Type

Option Code

/BR3

Wall Mount Bracket


Ordering Examples:

ARS15B-500

ARS15B-600

ARS15B-500/BR3

ARS15B-600/BR3

Old Ordering Examples:

ARS15B-000

ARS15B-100

ARS15B-000/BR3

ARS15B-100/BR3


Solid State Relay Boards (Contact Input)

Models

ARS15B-5 (48 V DC), ARS15B-6 (110 V DC)

Usage

Solid State Relay Contact Input (Single / Dual-redundant)

Contact Points

32-point

Terminals for Field Device Connection

M4 screws

Modules

ADV151 (DI: 32-point) + ATD5A (Terminal block) ADV161 (DI: 64-point) (*1)

Signal Cables

AKB331 (for 32-point) AKB337 (for 64-point)

Contact Input Signal

ON signal: 200 or less

OFF signal: At least 200 k

External Contact Rating

ARS15B-5 (48 V DC): At least 60 V DC, 20 mA ARS15B-6 (110 V DC): At least 140 V DC, 20 mA

Power Supply Voltage and Current

Consumption of Internal Circuit

(require external power supply)

24 V DC Max. 0.32 A

Power Supply for Field Device

(require external power supply)

Dual-line (supply power per 32-point)

ARS15B-5 (48 V DC): 48 V DC; Max. 0.5 A per one line

ARS15B-6 (110 V DC): 110 V DC; Max. 0.4 A per one line

Insulation Resistance

At least 10 M (500 V DC)

Withstanding Voltage

Between field device terminals and cases: 2 kV Between 24 V power terminals and cases: 500 V

Between 24 V power terminals and field device terminals: 2 kV

Ambient Temperature and Humidity

0 to 50 °C, 10 to 90 %RH

Standards

Safety standard [CSA] (*2), EMC standards [CE Marking], [C-Tick Marking],

[KC Marking]

Size

W: 482.6 mm x H: 132.5 mm (3U)

Weight

2.5 kg

#
copyright 2009-2021  HT INDUSTRIAL AUTOMATION LIMITED