ARM15A


YOKOGAWA
ARM15A 32 Dry Contact Inputs (M4 Terminals)


YOKOGAWA Relay Boards (for FIO):

ARM15A, ARM55D, ARM55W, ARM55T, ARM55C, ARS15B, ARS15M, ARS55M


GENERAL

This document describes the specifications of relay board used in FIO subsystem of CENTUM VP. Relay input/ output boards are connected in between digital input/output modules (for FIO) and field devices. Relay input boards receive contact signals or voltage input signals of field devices. Relay output boards receive output signals of the digital output module and amplify by the relay, and then output to field devices.   These relay boards support dual- redundant digital input/output modules (for FIO).


MODELS
 AND SUFFIX CODES

Mechanical Relay Board

Description

Model

ARM15A

32 Dry Contact Inputs (M4 Terminals)

Sufx Codes

-0

Always 0

0

19-inch Rack Mountable

0

Basic Type

Option Code

/BR3

Wall Mount Bracket


Ordering Examples:

ARM15A-000

ARM15A-000/BR3


Relay
 Boards Detail Specifications

Mechanical Relay Boards (Contact Input)

Model

ARM15A

Usage

Mechanical Relay Contact Input (Single / Dual-redundant)

Contact Points

32-point

Terminals for Field Device Connection

M4 screws

Modules

ADV151 (DI: 32-point) + ATD5A (Terminal block) ADV161 (DI: 64-point) (*1)

Signal Cables

AKB331 (for 32-point) AKB337 (for 64-point)

Contact Input Signal

ON signal: 150 or less

OFF signal: At least 200 k

External Contact Rating (Minimum Load)

24 V DC, 13 mA (*3)

Power Supply Voltage and Current

Consumption of Internal Circuit

(require external power supply)

24 V DC Max. 0.32 A

Power Supply for Field Device

(require external power supply)

Dual-line (supply power per 16-point)

24 V DC: Max. 0.3 A per one line

Insulation Resistance

At least 10 M (500 V DC)

Withstanding Voltage

Between field device terminals and cases: 1.5 kV Between 24 V power terminals and cases: 500 V

Between 24 V power terminals and field device terminals: 1.5 kV

Ambient Temperature and Humidity

0 to 50 °C, 10 to 90 %RH

Standards

EMC standards [CE Marking], [C-Tick Marking], [KC Marking] (*2)

Size

W: 482.6 mm x H: 132.5 mm (3U)

Weight

2.2 kg

*1:   Two sets of relay board (ARM15A) and two sets of signal cable (AKB337) are required for one ADV161.

*2:   ARM15A does not conform to Safety Standard [CSA].

*3:   It is voltage/current that ARM15A applies to the external contact power supply.

#