YOKOGAWA digitalYEWFLO Vortex Flowmeters
(YOKOGAWA DY Series Vortex Flowmeters)
Yokogawa’s proprietary filter (SSP) for digital signal processing analyzes vortex signals and automatically selects the optimum settings for the best possible measurement.
The digital YEWFLO vortex flowmeter combines the field proven sensor and body assembly used in more than 260,000 units installed worldwide with a unique and powerful combination of digital technology that includes spectral signal processing (SSP), a Yokogawa innovation. The digitalYEWFLO vortex flowmeter is accurate and stable, even in harsh process conditions, and has a highly reliable and robust design that delivers improvements in plant efficiency and reduced operating costs.
Ordering Examples:
1) DY Vortex Flowmeter (Integral Type, Remote type detector):
YOKOGAWA DY015-DALAA1-2D
YOKOGAWA DY025-EALAJ2-0D
YOKOGAWA DY040-EALAD4-4D
YOKOGAWA DY050-EBLBJ4-2N
YOKOGAWA DY080-JALBA5-0N
YOKOGAWA DY100-JBLBS1-4N
YOKOGAWA DY150-FALBD2-2D
YOKOGAWA DY200-EBECA4-2N
YOKOGAWA DY250-DBLAD2-4D
YOKOGAWA DY300-DBLAA2-2D
2) DYA Vortex Flowmeter Converter(Remote Type)
YOKOGAWA DYA-D2D
YOKOGAWA DYA-E2D
YOKOGAWA DYA-D0D
YOKOGAWA DYA-D0N
YOKOGAWA DYA-E0N
YOKOGAWA DYA-E0D
YOKOGAWA DYA-D4D
YOKOGAWA DYA-E4D
YOKOGAWA DYA-D4N
YOKOGAWA DYA-E4N
YOKOGAWA DYA-D2N
YOKOGAWA DYA-E2N
3) DYC Signal Cable:
YOKOGAWA DYC-0-05/C1/MV
YOKOGAWA DYC-1-10/C2/MV
YOKOGAWA DYC-0-15/C3/MV
YOKOGAWA DYC-1-20/C4/MV
YOKOGAWA DYC-0-25/C5/MV
YOKOGAWA DYC-1-30/C6/MV
YOKOGAWA DYC-0-35/C7/MV
YOKOGAWA DYC-1-40/C8/MV
YOKOGAWA DYC-0-45/C9/MV
YOKOGAWA DYC-1-50/C1/MV
YOKOGAWA DYC-0-55/C2/MV
YOKOGAWA DYC-1-60/C3/MV
YOKOGAWA DYC-0-65/C4/MV
YOKOGAWA DYC-1-70/C5/MV
YOKOGAWA DYC-0-75/C6/MV
YOKOGAWA DYC-1-80/C4/MV
YOKOGAWA DYC-0-85/C5/MV
YOKOGAWA DYC-1-90/C6/MV
YOKOGAWA DYC-0-95/C7/MV
If you do not have complete model number, never mind, just supply us detailed parameters by email, we can choose model number and give you a quotation immediately.
Features: YOKOGAWA DY/ DYA Series Vortex Flowmeter
New functions with Spectral Signal Processing (SSP) technology
SSP analyses the fluid conditions inside the digitalYEWFLO vortex flowmeter and uses the data to automatically select the optimum adjustment for the application, providing features never seen before in a vortex flowmeter.
SSP accurately senses vortices in the low flow range, providing outstanding flow stability.
Advanced self-diagnostics
Application conditions such as high pipeline vibration and abnormal flow are predicted and indicated
High accuracy
±0.75% of reading (liquid)
±1.0% of reading (gas, steam)
Wide process temperature range
High temperature version up to 450 deg C
Cryogenic version minimum -196 deg C
Simple parameter settings
Frequently-used selections grouped together in a quick-access format decrease commissioning time
Clear, concise indicator
Convenient display of the simultaneous and total flow rates together with the process diagnosis
Dual output for analog/pulse
Simultaneous output for flow rate and pulse
Alarm output
An alarm signal is output when an alarm occurs.
BRAIN/HART communication and key switches for human-machine interface
NACE compliant
NAMUR 43 compliant
Remote cable length up to 30m
Specifications: YOKOGAWA DY Series Vortex Flowmeters
|
Standard |
Multi-Variable |
Reduced Bore |
Model & code |
DY Vortex Flowmeter |
Optional code:/MV |
Option code:/R1,/R2 |
Fluid to be measured |
Liquid, gas, steam (avoid multiphase flow and sticky fluids) |
Nominal size |
15mm ∼ 300mm (400mm:special) |
25mm ∼ 200mm |
25mm ∼ 200mm |
Accuracy |
Liquid: ±1.0% of reading (20000≤Re≤1000) Liquid: ±0.75% of reading (D×1000≤Re) |
Liquid: ±1.0% of reading (20000≤Re≤1000) |
Gas, steam: ±1.0% of reading (flow velocity less than 35m/s) Gas, steam: ±1.5% of reading (flow velocity 35m/s ∼ 80m/s) |
Output signal |
Simultaneous output(both analog and transistor contact output available) |
Process temperature range |
-29 deg C - 260 deg C (standard) |
-29 deg C - 260 deg C (standard) |
-29 deg C - 260 deg C (standard) |
-196 deg C∼100 deg C (option: cryogenic version) |
N/A |
N/A |
-29 deg C∼450 deg C (option: high process temperature version) |
N/A |
-29 deg C∼450 deg C (option: high process temperature version) |
Process pressure limit |
-0.1MPa (-1kg/cm2) to flange rating |
Ambient temperature |
-29 to 85 deg C (Integral type / No indicator) -29 to 80 deg C (Integral type / with indicator) -29 to 85 deg C (Remote type detector) -40 to 85 deg C (Remote type converter / No indicator) -30 to 80 deg C (Remote type converter / with indicator) |
Ambient humidity |
5~100%RH( Non-condensing) |
Mounting |
Integral type and Remote type detector: Flange mounting or wafer mounting Remote type converter: 2 inch pipe mounting JIS10/20/40, ANSI150/300/600/900, JPI150/300/600,DIN PN10/16/25/40 |
Electrical connection |
JIS G1/2 female, ANSI 1/2NPT female, ISO M20×1.5 female |
Electrical classification |
JIS flameproof, FM explosion proof/intrinsically safe ATEX (CENELEC flameproof/intrinsically safe/IEC type n) CSA explosion proof/intrinsically safe : Dual Seal SAA flame proof/intrinsically safe |
Material |
Body: SCS14A cast stainless steel (equivalent to SUS316,CF8M) Shedder bar: duplex stainless steel (option:anti-corrosion version) Gasket: SUS316 stainless steel with polytetrafluoroethylene (Teflon) coating Converter housing and case cover: aluminum alloy or ASTM CF8M (equiv. JIS SCS14A) (Option: /E1) |
Applicable Standard |
*EMC Conformity Standards: EN61326-1 Class A, Table 2 (For use in industrial locations), EN61326-2-3 EN55011 Class A Group 1 *Pressure Equipment Directive: Notified Body Identification Number 0038 Module H |