HT INDUSTRIAL AUTOMATION LIMITED

 
YOKOGAWA MY10 SERIES OF ANALOG TESTERS

YOKOGAWA MY10 SERIES OF ANALOG TESTERS

  • Analog models with single rating
    MY10-01:125V/20MΩ
    MY10-02:250V/50MΩ
    MY10-03:500V/100MΩ
    MY10-04:500V/1000MΩ
    MY10-05:1000V/2000MΩ
  • AC voltage measurement
  • Automatic discharge
  • A wide choice of accessories-Designed for shared use with the MY40

Specifications - Model MY10-01

Rating

125V/20MΩ

Effective Measuring Range

0.01-20MΩ

Central Scale Value

0.5MΩ

AC Voltage Measurement

0 to 250 V

Lower Limit

0.125MΩ

Rated Current

1-1.2 mA

Approx. Overall Scale Length

107 mm

Battery Life

Approx. 10 hours when continuously operated on manganese - oxide batteries with the pointer pointing to the central scale value.

Batteries

Four AA (R6P) batteries

Approx. Width

125 mm

Approx. Height

103 mm

Approx. Depth

53 mm

Approx. Weight

500 g

Compliance

EN61010-1:1993; EN61010-2-31:1995 (Overvoltage Category III, Pollution Degree 2 installations for indoor use)

Standard Accessories

Batteries (Qty - 4)
Earth Probe (98002) (Qty - 1)
Line Probe (98001) (Qty - 1)
Protection Cover (93013) (Qty - 1)
Shoulder Strap (99005) (Qty - 1)
User's Manual (Qty - 1)

Standard Test Conditions - Model MY10-01

Ambient Temperature/Humidity Ranges

23 ±5 /45-75% RH

Position of Use

Horizontal (5° max. of angle of inclination)

Battery Voltage

Within effective voltage range (The pointer must stay within the range indicated by the BAT symbol when the battery check is performed.)

Tolerance Mentioned Conditions

Resistance measurement: First effective measuring range = ±5% of reading
Second effective measuring range = ±10% of reading
Infinite and zero scale values: 0.7% max. of scale length
AC voltage: ±10% of maximum scale value
No-load voltage: 130% max. of rated voltage
Rated measuring current: 1 mA (0 to 20%) when in first effective measuring range
Short-circuit current: 12 mA max.

Additional Functions - Model MY10-01

  • Automatic discharge function
    • If the object under test remains electrified after the MEAS switch is turned off, the tester lets you know by turning on the LED lamp. If you leave the tester connected to the electrified object, the tester automatically begins to discharge electricity and then finishes discharging-the LED lamp comes on and then goes out.
    • When the object under test is capacitive and electrified, the tester lets you know by turning on the LED lamp. When left connected to the object, the tester automatically discharges electricity, thus preventing possible electric shock or spike noise at power-on.
  • Battery check (BAT mark on the scale plate)

Specifications - Model MY10-02

Rating

250V/50MΩ

Effective Measuring Range

0.01-50MΩ

Central Scale Value

1MΩ

AC Voltage Measurement

0 to 300 V

Lower Limit

0.25MΩ

Rated Current

1-1.2 mA

Approx. Overall Scale Length

107 mm

Battery Life

Approx. 10 hours when continuously operated on manganese - oxide batteries with the pointer pointing to the central scale value.

Batteries

Four AA (R6P) batteries

Approx. Width

125 mm

Approx. Height

103 mm

Approx. Depth

53 mm

Approx. Weight

500 g

Compliance

EN61010-1:1993; EN61010-2-31:1995 (Overvoltage Category III, Pollution Degree 2 installations for indoor use)

Standard Accessories

Batteries (Qty - 4)
Earth Probe (98002) (Qty - 1)
Line Probe (98001) (Qty - 1)
Protection Cover (93013) (Qty - 1)
Shoulder Strap (99005) (Qty - 1)
User's Manual (Qty - 1)

Standard Test Conditions - Model MY10-02

Ambient Temperature/Humidity Ranges

23 ±5 /45-75% RH

Position of Use

Horizontal (5° max. of angle of inclination)

Battery Voltage

Within effective voltage range (The pointer must stay within the range indicated by the BAT symbol when the battery check is performed.)

Tolerance Mentioned Conditions

Resistance measurement: First effective measuring range = ±5% of reading
Second effective measuring range = ±10% of reading
Infinite and zero scale values: 0.7% max. of scale length
AC voltage: ±10% of maximum scale value
No-load voltage: 130% max. of rated voltage
Rated measuring current: 1 mA (0 to 20%) when in first effective measuring range
Short-circuit current: 12 mA max.

Additional Functions - Model MY10-02

  • Automatic discharge function
    • If the object under test remains electrified after the MEAS switch is turned off, the tester lets you know by turning on the LED lamp. If you leave the tester connected to the electrified object, the tester automatically begins to discharge electricity and then finishes discharging-the LED lamp comes on and then goes out.
    • When the object under test is capacitive and electrified, the tester lets you know by turning on the LED lamp. When left connected to the object, the tester automatically discharges electricity, thus preventing possible electric shock or spike noise at power-on.
  • Battery check (BAT mark on the scale plate)

Specifications - Model MY10-03

Rating

500V/100MΩ

Effective Measuring Range

0.05-100MΩ

Central Scale Value

2MΩ

AC Voltage Measurement

0 to 500 V

Lower Limit

0.5MΩ

Rated Current

1-1.2 mA

Approx. Overall Scale Length

107 mm

Battery Life

Approx. 10 hours when continuously operated on manganese - oxide batteries with the pointer pointing to the central scale value.

Batteries

Four AA (R6P) batteries

Approx. Width

125 mm

Approx. Height

103 mm

Approx. Depth

53 mm

Approx. Weight

500 g

Compliance

EN61010-1:1993; EN61010-2-31:1995 (Overvoltage Category III, Pollution Degree 2 installations for indoor use)

Standard Accessories

Batteries (Qty - 4)
Earth Probe (98002) (Qty - 1)
Line Probe (98001) (Qty - 1)
Protection Cover (93013) (Qty - 1)
Shoulder Strap (99005) (Qty - 1)
User's Manual (Qty - 1)

Standard Test Conditions - Model MY10-03

Ambient Temperature/Humidity Ranges

23 ±5 /45-75% RH

Position of Use

Horizontal (5° max. of angle of inclination)

Battery Voltage

Within effective voltage range (The pointer must stay within the range indicated by the BAT symbol when the battery check is performed.)

Tolerance Mentioned Conditions

Resistance measurement: First effective measuring range = ±5% of reading
Second effective measuring range = ±10% of reading
Infinite and zero scale values: 0.7% max. of scale length
AC voltage: ±10% of maximum scale value
No-load voltage: 130% max. of rated voltage
Rated measuring current: 1 mA (0 to 20%) when in first effective measuring range
Short-circuit current: 12 mA max.

Additional Functions - Model MY10-03

  • Automatic discharge function
    • If the object under test remains electrified after the MEAS switch is turned off, the tester lets you know by turning on the LED lamp. If you leave the tester connected to the electrified object, the tester automatically begins to discharge electricity and then finishes discharging-the LED lamp comes on and then goes out.
    • When the object under test is capacitive and electrified, the tester lets you know by turning on the LED lamp. When left connected to the object, the tester automatically discharges electricity, thus preventing possible electric shock or spike noise at power-on.
  • Battery check (BAT mark on the scale plate)

Specifications - Model MY10-04

Rating

500V/1000MΩ

Effective Measuring Range

0.5-1000MΩ

Central Scale Value

20MΩ

AC Voltage Measurement

0 to 500 V

Lower Limit

1MΩ

Rated Current

0.5-0.6 mA

Approx. Overall Scale Length

107 mm

Battery Life

Approx. 10 hours when continuously operated on manganese - oxide batteries with the pointer pointing to the central scale value.

Batteries

Four AA (R6P) batteries

Approx. Width

125 mm

Approx. Height

103 mm

Approx. Depth

53 mm

Approx. Weight

500 g

Compliance

EN61010-1:1993; EN61010-2-31:1995 (Overvoltage Category III, Pollution Degree 2 installations for indoor use)

Standard Accessories

Batteries (Qty - 4)
Earth Probe (98002) (Qty - 1)
Line Probe (98001) (Qty - 1)
Protection Cover (93013) (Qty - 1)
Shoulder Strap (99005) (Qty - 1)
User's Manual (Qty - 1)

Standard Test Conditions - Model MY10-04

Ambient Temperature/Humidity Ranges

23 ±5 /45-75% RH

Position of Use

Horizontal (5° max. of angle of inclination)

Battery Voltage

Within effective voltage range (The pointer must stay within the range indicated by the BAT symbol when the battery check is performed.)

Tolerance Mentioned Conditions

Resistance measurement: First effective measuring range = ±5% of reading
Second effective measuring range = ±10% of reading
Infinite and zero scale values: 0.7% max. of scale length
AC voltage: ±10% of maximum scale value
No-load voltage: 130% max. of rated voltage
Rated measuring current: 1 mA (0 to 20%) when in first effective measuring range
Short-circuit current: 12 mA max.

Additional Functions - Model MY10-04

  • Automatic discharge function
    • If the object under test remains electrified after the MEAS switch is turned off, the tester lets you know by turning on the LED lamp. If you leave the tester connected to the electrified object, the tester automatically begins to discharge electricity and then finishes discharging-the LED lamp comes on and then goes out.
    • When the object under test is capacitive and electrified, the tester lets you know by turning on the LED lamp. When left connected to the object, the tester automatically discharges electricity, thus preventing possible electric shock or spike noise at power-on.
  • Battery check (BAT mark on the scale plate)

Specifications - Model MY10-05

Rating

1000V/2000MΩ

Effective Measuring Range

1-2000MΩ

Central Scale Value

50MΩ

AC Voltage Measurement

0 to 500 V

Lower Limit

2MΩ

Rated Current

0.5-0.6 mA

Approx. Overall Scale Length

107 mm

Battery Life

Approx. 10 hours when continuously operated on manganese - oxide batteries with the pointer pointing to the central scale value.

Batteries

Four AA (R6P) batteries

Approx. Width

125 mm

Approx. Height

103 mm

Approx. Depth

53 mm

Approx. Weight

500 g

Compliance

EN61010-1:1993; EN61010-2-31:1995 (Overvoltage Category III, Pollution Degree 2 installations for indoor use)

Standard Accessories

Batteries (Qty - 4)
Earth Probe (98002) (Qty - 1)
Line Probe (98001) (Qty - 1)
Protection Cover (93013) (Qty - 1)
Shoulder Strap (99005) (Qty - 1)
User's Manual (Qty - 1)

Standard Test Conditions - Model MY10-05

Ambient Temperature/Humidity Ranges

23 ±5 /45-75% RH

Position of Use

Horizontal (5° max. of angle of inclination)

Battery Voltage

Within effective voltage range (The pointer must stay within the range indicated by the BAT symbol when the battery check is performed.)

Tolerance Mentioned Conditions

Resistance measurement: First effective measuring range = ±5% of reading
Second effective measuring range = ±10% of reading
Infinite and zero scale values: 0.7% max. of scale length
AC voltage: ±10% of maximum scale value
No-load voltage: 130% max. of rated voltage
Rated measuring current: 1 mA (0 to 20%) when in first effective measuring range
Short-circuit current: 12 mA max.

Additional Functions - Model MY10-05

  • Automatic discharge function
    • If the object under test remains electrified after the MEAS switch is turned off, the tester lets you know by turning on the LED lamp. If you leave the tester connected to the electrified object, the tester automatically begins to discharge electricity and then finishes discharging-the LED lamp comes on and then goes out.
    • When the object under test is capacitive and electrified, the tester lets you know by turning on the LED lamp. When left connected to the object, the tester automatically discharges electricity, thus preventing possible electric shock or spike noise at power-on.
  • Battery check (BAT mark on the scale plate)
#
copyright 2009-2021  HT INDUSTRIAL AUTOMATION LIMITED