YOKOGAWA CLAMP-ON TESTER FOR LEAKAGE CURRENT #CL320 |
YOKOGAWA CLAMP-ON TESTER FOR LEAKAGE CURRENT #CL320
Clamp-on Testers For Leakage Current
- Leakage current measurement with current range from 20mA to 200A
- Light weight and compact design
- Manual range switching and auto power-off functions
- 24mm in diameter of measurable conductor
- Mean value display
- Auto power-off
- Manual range switching
- Approved for comformity to safety standards EN61010-1, EN61010-2-032(CAT. III 300 V)
Specifications
Description |
Leakage Current Mini Clamp-on |
Method of detection |
Mean Value |
Display |
LCD (Digital display: 1999 counts) |
Response Time |
Approx. 2 seconds |
Range Switching |
Manual-range |
Data hold |
On all range |
Operating temperature and humidity |
0 - 40°C, 85% RH or less (no condensation) |
Influence of external magnetic field |
10 mA or less in proximity to a 14.4 mm-dia conductor carrying 100A |
Influence of conductor position |
Within 5 dgt for 0 to 50A, or 2% for 50 to 200A (10 mm-dia conductor at inside the jaw) |
Influence of Residual Current |
10 mA or less in proximity to a 10 mm-dia conductor carrying 50A |
Safety Standard |
Conforms EN61010-1, EN61010-2-032 |
Circuit voltage |
300 Vrms or less |
Withstanding voltage |
3.7 kV AC for one minute |
Power Supply |
LR-44 x 2(3V) SR-44 x 2 |
Battery Life |
Approx. 15 hours (continuous) |
Consumed current |
Approx. 5 mA |
Auto power-off |
Approx. 10 minutes |
Diameter of measurable conductor |
24 mm at maximum |
Dimensions |
Approx. 60 (W) x 149 (H) x 26 (D) mm |
Weight |
Approx. 120 g |
Accessories |
Batteries, carrying case (93033) User's manual (IM CL320) |
Selection Guide
DC Current Range |
- |
DC Current Resolution |
- |
AC Current Range |
20/200mA,200A |
AC Current Resolution |
0.01mA |
AC Current Frequency characteristics |
40~400Hz |
AC Current Method of detection |
Mean Value |
AC Voltage Measurement |
- |
DC Voltage Measurement |
- |
Continuity Check Measurement |
- |
Frequency Measurement |
- |
Temperature Measurement |
- |
Recorder output Function |
- |
Waveform monitor output Function |
- |
Data hold Function |
O |
Auto hold Function |
- |
Peak Hold Function |
- |
Maximum value memory Function |
- |
Mean value display Function |
- |
Filter Function |
O |
Range Hold Function |
O |
Auto ZERO Adjust Function |
- |
Auto power-off Function |
O |
Additional Specification
At 23°C±5°C,75%RH or less |
Accuracy: ±( % rdg + dgt) = ±(% readout + value of least significant digit) |
Parameter |
Reference |
Accuracy |
WIDE(40~400Hz) |
50/60Hz |
AC current |
20mA/200mA |
2.0+4 (50/60Hz) |
3.0+5 (50/60Hz) |
200A(0~100A) |
5.0+6 (40~400Hz) |
200A(100.1~200A) |
5.0+4 (50/60Hz) |
5.0+5 (50/60Hz) | |
|